The regulatory position
ACOP L8 and HSG274 Part 2 require cold water storage tanks to be inspected and, where necessary, cleaned and disinfected. They do not specify "once a year" as a legal minimum. What they require is that the frequency is justified by a site-specific assessment of risk.
In practice most well-run sites inspect tanks at least annually and clean when the inspection shows it is needed — sediment, biofilm, rust, scale, damaged lids or insulation. Many organisations simply programme an annual clean because it makes the schedule predictable, and for tanks in high-demand buildings that is a reasonable position.
What changes the interval
A tank serving a soft-water area with high dissolved solids will silt up faster than one on a clean supply. Galvanised steel tanks that have lost their zinc coating corrode and shed debris. Tanks with ill-fitting lids, damaged insect screens or uninsulated cold-feed pipework let contamination and warmth in. Buildings with intermittent use — student halls, seasonal hotels, offices with partial occupancy — leave water standing for long periods and tend to need more frequent attention, as do systems that have previously returned unsatisfactory samples.
- Annual inspection as a starting minimum, more often where condition is poor
- Clean when sediment, biofilm, corrosion or scale is visible
- Sooner after a positive Legionella or coliform result, or a contamination event
- Sooner after building works, flooding or long vacancy
What an inspection should actually look for
A meaningful inspection is not a glance through a hatch. It should confirm the tank is structurally sound, that the lid fits and is insulated, that insect and vermin screens are intact, that the water temperature is below 20°C, that the ball valve and overflow are functioning, that there is no cross-connection or dead leg, and that no sediment or biofilm is present. Condition of the internal surfaces determines whether cleaning alone is enough or whether relining or refurbishment should be planned.
What a clean involves
Isolation, drain-down, internal inspection, mechanical cleaning of all internal surfaces, chlorination at the specified concentration with a recorded contact time, neutralisation, flushing and refill, followed by post-disinfection sampling and a certificate. Anything less than that is a partial job and should be described as such in the report.
This article is general guidance, not a site-specific risk assessment. Control measures for your building should follow your written scheme of control and the Approved Code of Practice L8 with HSG274.