Thermostatic mixing valve filters stripped down for inspection on a clinical washbasin
Scalding Risk Control

TMV Servicing & Testing
Yorkshire & Nationwide

Thermostatic mixing valves are critical safety devices. Our planned TMV servicing keeps them delivering water at a safe temperature, proves fail-safe operation, and gives you the written records required for healthcare, education and social housing compliance.

What the service covers

A thermostatic mixing valve blends hot and cold water to a controlled outlet temperature, protecting users from scalding at basins, baths, showers and clinical outlets. Like any mechanical safety device, a TMV drifts out of calibration as internal components scale up, and a valve that fails can deliver water hot enough to cause serious injury within seconds.

We service TMVs to the manufacturer instructions and D08 scheme requirements: measuring inlet and outlet temperatures, testing the fail-safe function by isolating the cold supply, checking flow rates and cleaning or replacing strainers and filters. Valves outside tolerance are adjusted, repaired or scheduled for replacement.

Our engineers maintain TMV schedules for care homes, hospitals, schools, nurseries, hotels, leisure centres and residential blocks throughout Bradford, Leeds and West Yorkshire, with asset registers and tagged outlets so every valve is tested on a defined cycle.

Our process, step by step

01Visual inspection of the valve, isolation valves and associated pipework
02Temperature measurement at inlet and outlet under operating conditions
03Fail-safe testing with hot and cold supply isolation
04Flow rate assessment and adjustment to specification
05Strainer and filter cleaning or replacement
06Calibration to the specified safe outlet temperature range
07Performance verification and outlet labelling
08Service documentation and compliance reporting per the D08 TMV Scheme