Water System Disinfection
Tanks, Pipework & New Installations
Whole-system chlorination where the problem is not confined to a tank — after a positive result, following building works, before a new system is handed over, or when a building has stood empty.
What the service covers
Disinfecting a storage tank solves the tank. It does not solve the pipework, the dead legs, the little-used WC on the top floor, or the shower range that shares a riser with the affected tank. Where a system has been contaminated, altered or shut down, the whole distribution needs treating and then verifying by sampling.
We chlorinate to a controlled concentration, hold it for the required contact time, then neutralise and flush the system thoroughly before returning it to service. Every stage is measured and recorded: dose, concentration at representative points, contact time, flush volumes and final residual. Where a system can be isolated in sections we do that, so parts of the building can stay operational throughout.
The same process is used for new and altered installations, where a clean, flush and disinfection certificate is required before handover. If you are a contractor or M&E firm needing disinfection documentation for a completed project, we can attend at commissioning, carry out the works and issue the certificate the client needs for their building manual.
Our process, step by step
Frequently asked questions
When is whole-system disinfection needed, rather than just cleaning the tank?
Tank cleaning addresses the storage vessel; whole-system disinfection addresses the pipework, outlets and terminal fittings downstream. It is typically needed after a positive Legionella or coliform result, after works on the system, at handover of new or altered pipework, when a building has been vacant, or where a system has been contaminated by flooding or works debris.
Can the building stay open during disinfection?
Sometimes, sometimes not. It depends on whether the system can be split into sections, whether alternative supply or temporary outlets exist, and whether occupants must be excluded from areas while disinfectant is present. We assess this at survey and plan the works so you know the impact before we start.
How is disinfection verified?
Disinfectant concentration and contact time are recorded during the works, the system is then flushed and neutralised, and post-disinfection samples are taken for laboratory analysis. A disinfection certificate and sample results together form the evidence that the work achieved what it set out to do.
Do new installations need a disinfection certificate?
Yes. New and altered water systems should be cleaned, flushed and disinfected in line with HSG274 and BS 8558 before they are brought into service, and the certificate should be retained as part of the building water safety file and handed to the building operator at completion.